| 2001-01-08 00:00:00 | 1. PLANS MUST BE SPLIT INTO THREE |
| | SEPARATE SETS OF THREE SIGNED AND SEALED |
| | DOCUMENTS. |
| | 2. IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY. |
| | 3. PROJECT IS A FLORIDA THRESHOLD |
| | BUILDING.PROVIDE APPLICATION |
| | AND INSPECTION PLAN TO DON NEELY ABO, |
| | FOR REVIEW AND APPROVAL. SEE SHEET S-1 |
| | NOTE 3. |
| | 4. LANDINGS MUST MEET 1997 SBC SECTION |
| | 1007.4.2, SEE SHEET A-21, REFERENCE NOTE |
| | A-4 BRIDGE NOTE. |
| | 5. FIRE SEPARATION RATING, DETAILS AND |
| | OPENINGPROTECTION INFORMATION FOR |
| | RESIDENTIALTO COMMERCIAL SPACE SEE |
| | SHEET A-11AND SHEET A-12 REQUIRE |
| | SECTIONS AND FIRE RATINGS. |
| | 6. CERTIFICATION OF PLANS AS COMPLYING |
| | WITH FLORIDA STATUTE 553.79 AND FEDERAL |
| | FAIR HOUSING ACT, AUGUST 1996 AS REVISED |
| | APRIL 1998. |
| | 7. SHEET A-17 INDICATES THAT A SLOPE |
| | STARTS AT THE DOOR, A LANDING IS |
| | REQUIRED AT ALL DOORS PRIOR TO STARTING |
| | A SLOPE 1997 SBC SECTION 1012.1.3. |
| | 8. PRODUCT APPROVAL FOR ALL WINDOWS AND |
| | DOORS SBC 1997, 110 MPH WIND LOADS. |
| | 9. PRODUCT APPROVAL FOR GLAZING TO |
| | SHOW COMPLIANCEWITH IMPACT PROTECTION |
| | REQUIREMENTS. |
| | 10. FIRE RATING DOORS, DOOR 15, 16, 17, |
| | AND 22 REQUIRE B LABEL SHEET A-26 |
| | INDICATES C LABEL. |
| | 11. DOOR 20 TO EXCERISE ROOM TO BE 20 |
| | MINUTE RATED AND DOOR 21 TO OFFICE TO BE |
| | 3/4 HR. C LABELED DOOR. |
| | 12. SHEET A-27 IF HURRICANE SHUTTERS ARE |
| | TO BE USED PROVIDE. A) THE STORAGE |
| | LOCATION FOR ALL PANELSREQUIRED AND |
| | THE INSTALLATION PLAN FOR REVIEW AND |
| | APPROVAL. CHANGE REFERENCE IN NOTE 2 |
| | TO 1997 EDITION OF THE SBC AND SSTD |
| | 10-97, REFERENCE IS TO THE 1994 CODE AND |
| | STANDARD. |
| | 13. TRUSS DIAGRAMSFOR THE PROJECT. |
| | 14. SHEET A-44 MEET 1997 FLORIDA |
| | HANDICAPPED CODE FIGURE 19 FOR STAIR |
| | HANDRAILS, PAGE 99. |
| | 15. SHEET A-48 CHANGE NOTE TO REFERENCE |
| | 1997 SBC FOR ROOFING. |
| | 16. POOLS, SUBMIT TO HEALTH DEPT. FOR |
| | REVIEW AND APPROVAL, PROVIDE INFORMATION |
| | ON FENCING AND GATES AS REQUIRED BY CITY |
| | W.P.B. POOL CODE. SHEET A-54 |
| | 17. SHEET S-2 ETC. INDICATE SLUMP OF |
| | GROUT. |
| | |
| | 18. ADDITIONAL PERMIT FEES DUE. |
| | 19. CODE REFERENCES |
| | 1997 STANDARD BUILDING MECHANICAL AND |
| | GAS CODES |
| | 1996 NATIONAL ELECTRICAL CODE |
| | 1994 STANDARD PLUMBING CODE |
| | 1997 FLORIDA HANDICAPPED CODE |
| | 1997 FLORIDA ENERGY CODE |
| | 1996 FEDERAL FAIR HOUSING ACT AS AMENDED |
| | CITY OF WEST PALM BEACH AMENDMENTS TO |
| | THE CODES EFFECTIVE JULY 1, 1999. |
| | |
| | 20. CODE REVIEW IS FOR 630, 720 AND 780 |
| | SAPODILLA. |