Plan Review Notes
Plan Review Notes For Permit 99090699
Permit Number 99090699
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00SUBMIT OCCUPANT LOAD TO ENSURE
 COMPLIANCE W/SEC.407 AND TABLE 407 OF
 SPC.
  
 HANDICAP STALL SHALL COMPLY W/FACBC SEC.
 4.17.3(SEE EXCEPTION:NEW CONSTRUCTION)
  
 URINAL SHALL BE SCREENED FOR PRIVACY.
 PER SPC SEC.404.3 (LOCATED IN LINE OF
 SIGHT FROM VESTIBULE.)
  
 AMOUNT AND TYPE OF REQD.PLBG. FIXTURES
 SHALL COMPLY W/FLA.STATUTE 553.141(3).
  
 DISPENSERS IN H.C.TOILET STALL SHALL
 COMPLY W/FACBC SEC.4.22.7,4.27,AND FIG.
 30 OF FACBC.
  
 GRAB BAR BEHIND TOILET SHALL COMPLY W/
 FACBC FIG.30.
  
 RECEPTORS RECEIVING DISCHARGE FROM I.W.
 PIPES SHALL COMPLY W/SPC SEC.807.1.3.
 (FLOOR DRAINS NOT PERMITTED.)
  
 SUBMIT MANUF.SHEETS FOR ALL GAS EQUIP.
 EQUIP. SHALL BE LISTED/APPROVED PER STD.
 GAS CODE 402.1.
  
 MAX.TEMP. OF WATER TO RESTROOMS SHALL BE
 110 DEGREES PER FLA.ENERGY CODE SEC.
 412.1.ABCD.2.3.2.
  
 LOCATION OF BACKFLOW DEVICE SHALL BE
 APPROVED BY CITY OF WEST PALM BEACH
 UTILITY DEPT.
  
 CONTACT RODNEY COMPO AT CITY OF WEST
 PALM BEACH REGIONAL WASTEWATER TREATMENT
 PLANT FOR PROPER SIZE OF GREASE TRAP.
 (561)835-7423.
  
 HUB DRAINS ARE NOT PERMITTED PER SPC.
 FLOOR DRAINS SHALL BE INSTALLED.TABLE
 713.1
  
 CIRCUIT AND LOOP SYSTEM SHALL COMPLY W/
 SPC SEC.914.1 AND 920.3.
  
 DRY VENTS ARE NOT PERMITTED PER SPC SEC.
 901.2.
  
 MOP SINK REQUIRES INDIVIDUAL VENT PER
 COUNTYWIDE AMENDMENTS TO SPC SEC.911.1.1
  
 INDICATE TYPE OF PIPE MATERIAL TO BE
 INSTALLED FOR THE GAS SYSTEM AND
 INDICATE IF GAS IS NATURAL OR LP. PER
 S.G.C.SEC.302.
  
 SIZE GAS SUPPLY LINE TO THE APPLIANCE
 ON THE GAS RISER.S.G.C.302.
  
 INDICATE ON PLANS IF ALCOHOL WILL BE
 SERVED ON THE PREMISES.(WILL AFFECT
 FIXTURE REQS.)COMPLY W/TABLE 407 OF SPC.