2001-01-08 00:00:00CORRECTED BY REVISIONA
 CALC-30 CFM PER PERSON REQUIRED FOR AH4
 FAN SHUT DOWN TO BE TIED TO BLDG FIRE
 ALARM OR HORN AND STROBE FOR NOTIFICATIO
 N PER NFPA 90A 4-4.4.2 OR.3.