| Plan Review Notes For Permit 99090570 |
| Permit Number |
99090570 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | A DRINKING FOUNTAIN IS REQD.PER SPC | | | TABLE 407 AND SHALL COMPLY W/FACBC SEC. | | | 4.1.3(10)(A). | | | | | | FLOOR DRAINS ARE REQD.IN THE TOILET | | | ROOMS PER SPC 409.4.1.1,EXCEPTION. | | | | | | CLEARLY IDENTIFY THE CHANGES MADE TO THE | | | PLUMBING SYSTEM.COUNTYWIDE AMENDMENTS TO | | | SPC SEC.104.2.1. |
|