| 2001-01-08 00:00:00 | *************** UNSAT ****************** |
| | |
| | 1)NOTE:IT HAS COME TO MY ATTENTION THAT |
| | MORE WORK HAS BEEN DONE THAN ON ORIGINAL |
| | APPLICATION/PLANS. THE VALUE THAT WAS |
| | ON THE FIRST APPL. MUST BE INCREASED. |
| | |
| | 2)NOTE:IT IS MY UNDERSTANDING THAT THERE |
| | IS A WALL WITH LIGHTS AND LANDSCAPE |
| | LIGHTING THAT HAS BEEN DONE. THIS WAS |
| | NOT ON PLANS AND NOT ON PERMIT APPLICAT- |
| | -ION. YOU NEED TO SUBMIT A COMPLETE SET |
| | OF REVISED PLANS SHOWING ALL ELECTRICAL |
| | WORK THAT HAS BEEN DONE. PLEASE INCLUDE |
| | LIGHTING DETAIL ON WALL AND DETAILED |
| | LANDSCAPE LIGHTING. |
| | |
| | 3)NOTE:SMOKE DETECTORS ARE REQ`D INSIDE |
| | AND OUTSIDE ALL THE SLEEPING ROOMS PER |
| | NFPA-72 2-2.1.1.1 |
| | |
| | 4)NOTE: FLOODLIGHTS ON THE DETACHED |
| | GARAGE MUST HAVE A MEANS OF DISCONNECT |
| | OR THE POWER FOR THE FLOODLIGHTS MUST |
| | COME FROM THAT STRUCTURE AND FEED ONLY |
| | TO A THREE-WAY SWITCH IN THE MAIN HOUSE |
| | |
| | |
| | 5)NOTE: PLEASE SUBMIT A REVISED PANEL |
| | SCHEDULE AND PLEASE SHOW SIZE OF THE |
| | EXISTING SERVICE AND LOAD CALCULATION. |
| | |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| | FOR REVIEW. ALL THE ABOVE PER 215-5. |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL |
| | 659-8096 EXT 8372 |