Plan Review Notes
Plan Review Notes For Permit 99090467
Permit Number 99090467
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00WALLS IN TOILET ROOMS SHALL BE NON-
 ABSORBENT TO A HEIGHT OF 4'PER SBC SEC.
 1204.2.
  
 SUBMIT OCCUPANT LOAD PER TABLE 407 OF
 SPC.
  
 FLOOR DAINS ARE REQD.IN THE TOILET ROOMS
 PER SPC SEC.409.4.1.1.
  
 SINK IN LOUNGE SHALL COMPLY W/FACBC SEC.
 4.24.1-4.24.7.
  
 SECONDARY DRAINAGE FOR ROOF SHALL COMPLY
 W/SPC TABLE A101.2.
  
 SUBMIT STORM DRAINAGE RISER FOR REVIEW.
 SPC 104.2.1.