| Date |
Text |
| 2001-01-08 00:00:00 | PASSED WITH PROVISOS:TS (659-8040) |
| | WATER AND SANITARY:ONCERNING STORMWATER |
| | 1.DRAWINGS MUST BE THE ONES LAST REVISED |
| | AND APPROVED ON 11/19/99 STAMPED FORTA- |
| | HEALTH DEPARTMENT 11-23-99 WITH 2-2"ALED |
| | METERS AND A 4" PFL, AND A 6" LATERAL, |
| | ALL TO BE CONTRACTOR INSTALLED (ALL0); |
| | SHEETS, 6 OF 6).PPROVED THRU UTILITIES |
| | 2.ADDITIONALLY IF THE 11-23-99 REVISIONS |
| | DO NOT SHOW IT A CLEAN-OUT MUST BE |
| | PLACED AT THE BACK OF SIDEWALK, SEE CITY |
| | DETAIL ON SHEET 5 OF 6. |
| | 3.BACKFLOW PREVENTER LOCATION ON SHEETE- |
| | FS-1 IS WRONG.BACKFLOW PREVENTER BY |
| | (DCDA) WILL BE LOCATED AT BACK OF WALK. |
| | STORMWATER: |
| | PLAN SHEET 2 OF 6 AND CALCULATIONS |
| | SUBMITTED WITH 10-20-99 REVISED DATE OK. |
| | STREETS: |
| | 1.STOP SIGN ON SOUTHWEST EXIT IS TO BE |
| | AT BACK OF SIDEWALK, NOT AT CURB (SEE |
| | SHEET 2 OF 6) |
| | 2.STOP SIGN ON NORTHEAST EXIT IS TO BE |
| | AT BACK OF SIDEWALK, NOT IN DRIVEWAY |
| | RAMP (SEE SHEET 2 OF 6).THE PARKING |
| | LOT LIGHT ON SHEET SP-1 MAY INTERFERE |
| | WITH THIS STOP SIGN, PERHAPS THE STOP |
| | SIGN CAN BE MOUNTED TO THE LIGHT POLE, |
| | BUT THE LIGHT POLE SHOULD NOT BE THAT |
| | CLOSE TO THE DRIVEWAY. |
| | 3.BOTH DRIVEWAY RAMPS ARE TO BE CONCRETE |
| | AND TO THE CITY DETAILS (SEE ATTACHED). |
| | 4.I CAN NOT FIND ON THE DRAWINGS A |
| | STATEMENT THAT THE EXISTING DRIVEWAYS |
| | WILL BE REMOVED BY THE CONTRATOR, THEY |
| | WILL BE REMOVED BY THE CONTRACTOR AND |
| | REPLACED WITH CURBS THAT MATCH THE |
| | EXISTING. |
| | 5.LANDSCAPING (PALM TREES) CAN NOT BE |
| | PLACED OVER THE WATER MAIN ON FLAGLER, |
| | REMOVE THEM (SEE SHEET 1/4 BY |
| | ENVIRONMENTAL DESIGN GROUP). |
| | 6. IT IS MANDATORY THAT PLANTS BE PLACED |
| | AROUND THE BACKFLOW PREVENTERS SHOWN ON |
| | SHEET 2 OR 6 BY SIMMONS AND WHITE. |
| | 7. SHEET E-1 DOES NOT SHOW THE TWO POLE |
| | MOUNTED PARKING LOT LIGHTS SHOWN ON |
| | SHEET SP-1 NEXT TO EACH DRIVEWAY. |
| | DUMPSTER ENCLOSURE: |
| | 1.OK, EXCEPT, THE PLUMBING PLAN DOES NOT |
| | SHOW THE WATER LINE TO THE DUMPSTER AS |
| | SHOWN ON PAGE SP-2 AND REFERRING TO THE |
| | PLUMBING PLAN P-2, 3 OR 4. |