2001-01-08 00:00:00SUBMIT A GAS RISER DIAGRAM FOR REVIEW.
 SHOW TYPE OF PIPING MATERIAL,ALL LINE
 SIZES,BTU LOAD OF EACH APPLIANCE AND
 TOTAL BTU LOAD ON SYSTEM.INDICATE ON
 PLAN HOW PIPING WILL BE INSTALLED UNDER
 BLDG.COMPLY W/S.G.C. SEC.308.3.1,308.3.2
  
 SUBMIT A SANITARY RISER DIAGRAM THAT
 CLEARLY SHOWS ALL NEW WORK.COUNTYWIDE
 AMENDMENTS TO STD.GAS CODE SEC.104.2.1.
  
 PLBG.FIXTURES LOCATED DOWNSTREAM OF
 WATER CLOSETS SHALL BE VENTED PER SPC
 913.2.
  
 GAS INSTALLATION SHALL BE PERFORMED BY
 QUALIFIED PERSONNEL PER NFPA 54 SEC.1.4.