| Plan Review Notes For Permit 99090379 |
| Permit Number |
99090379 |
|
| Review Stop |
P |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | DRY VENTS NOT PERMITTED.SPC 906.2.1. | | | | | | MAX.20 FIXTURE UNITS PERMITTED TO | | | DISCHARGE INTO 3" HORIZ.BRANCH PER SPC | | | TABLE 714.1.,714.2. | | | | | | SIZE ALL SECTIONS OF THE SANITARY SYSTEM | | | AT SERVING STATION #1.COUNTYWIDE AMEND- | | | MENTS TO STD.PLBG.CODE SEC.104.2.1. | | | | | | INSTALLATION OF CIRCUIT AND LOOP SYSTEM | | | SHALL COMPLY W/SPC 914.1. | | | | | | CLEANOUTS SHALL BE INSTALLED PER SPC SEC | | | 710.2.1. | | | | | | MAX.2 FIXTURES SHALL BE SUPPLIED BY 1/2" | | | C.W.AND 4 FIXTURES BY 1/2" H.W.PER | | | COUNTYWIDE AMENDMENTS TO STD.PLBG.CODE | | | SEC.607.7. | | | | | | SIZING OF GAS SYSTEM SHALL COMPLY W/SGC | | | TABLE 305.4(A). | | | | | | GAS SHUT-OFF VALVES SHALL BE LOCATED | | | BELOW CEILING PER NFPA SEC.3.3.4.VALVE | | | AND UNION ARRANGEMENT SHALL BE INSTALLED | | | PER NFPA SEC.5.5.4. |
|