Plan Review Notes
Plan Review Notes For Permit 99090379
Permit Number 99090379
Review Stop P
Sequence Number 4
Notes
Date Text
2001-01-08 00:00:00DRY VENTS NOT PERMITTED.SPC 906.2.1.
  
 MAX.20 FIXTURE UNITS PERMITTED TO
 DISCHARGE INTO 3" HORIZ.BRANCH PER SPC
 TABLE 714.1.,714.2.
  
 SIZE ALL SECTIONS OF THE SANITARY SYSTEM
 AT SERVING STATION #1.COUNTYWIDE AMEND-
 MENTS TO STD.PLBG.CODE SEC.104.2.1.
  
 INSTALLATION OF CIRCUIT AND LOOP SYSTEM
 SHALL COMPLY W/SPC 914.1.
  
 CLEANOUTS SHALL BE INSTALLED PER SPC SEC
 710.2.1.
  
 MAX.2 FIXTURES SHALL BE SUPPLIED BY 1/2"
 C.W.AND 4 FIXTURES BY 1/2" H.W.PER
 COUNTYWIDE AMENDMENTS TO STD.PLBG.CODE
 SEC.607.7.
  
 SIZING OF GAS SYSTEM SHALL COMPLY W/SGC
 TABLE 305.4(A).
  
 GAS SHUT-OFF VALVES SHALL BE LOCATED
 BELOW CEILING PER NFPA SEC.3.3.4.VALVE
 AND UNION ARRANGEMENT SHALL BE INSTALLED
 PER NFPA SEC.5.5.4.