Plan Review Notes
Plan Review Notes For Permit 99090379
Permit Number 99090379
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00MOP SINK REQUIRES INDIVIDUAL VENT PER
 COUNTYWIDE AMENDMENTS TO STANDARDPLBG.
 CODE SEC.911.1
  
 PLANS SHALL BE REVIEWED AND APPROVED BY
 DEPT.OF BUSINESS REGULATION PRIOR TO
 APPROVAL BY THE CITY OF W.P.B.BLDG.DEPT.
 PER SPC SEC.101.4.7.
  
 FLOOR SINKS BY BUFFET AREA NOT SHOWN ON
 SANITARY RISER AND ARE NOT PROPERLY
 VENTED.SPC SEC.908.1 & TABLE 908.1.
  
 WATER CLOSETS AND FIXTURE BRANCHES NOT
 PERMITTED ON WET VENTS PER COUNTYWIDE
 AMENDMENTS TO PLBG.CODE SEC.911.1.
  
 NO MORE THAN 2 WATER CLOSETS ARE
 PERMITTED ON 3" DRAIN PER TABLES 714.1 &
 714.2 FOOTNOTES #3 AND #2.
  
 SIZE ALL SECS.OF THE DRAIN, WASTE AND
 VENT SYSTEM.SPC 104.2.1.
  
 SIZE ALL SECTIONS OF THE WATER RISER.SPC
 SEC.104.2.1.
  
 SIZE ALL SECTIONS OF THE GAS RISER PER
 STD.GAS CODE SEC.302 AND NFPA 54.
  
 ALL GAS EQIUPMENT SHALL BE APPROVED PER
 STD.GAS CODE 402 AND NFPA 54.SUBMIT
 MANUF.SHEETS.
  
 WATER SUPPLY CONTROL SHALL COMPLY W/SPC
 SEC.610.4.1, 610.4.2.
  
 OVER 2 FIXTURES SUPPLIED BY 1/2" C.W.
 LINE.PER COUNTYWIDE AMENDMENTS SEC.607.7
  
 NO "M" COPPER PERMITTED U/G.PER COUNTY-
 WIDE AMENDMENTS TO PLBG.CODE SEC.611.3.
  
 COMPLY W/PREVIOUS COMMENTS DATED 10/7/99
  
 REVISIONS SHALL BE ATTACHED TO MASTER
 SET OF PLANS.