| 2001-01-08 00:00:00 | 1) SUBFEED TO PANEL "A" TO SMALL OR FUSE | | | TO BIG 240-3 ALLOWS NEXT STANDARD SIZ | | | WHICH IS 350A !!! | | | 2) DINING ROOMS DO NOT HAVE ENOUGH OUT- | | | LETS LOCAL CODE CALLS FOR OUTLETS | | | EVERY 20' ON CENTER!! CHECK OTHER | | | AREAS!! | | | 3) SUBMIT INFORMATION BEFORE 1ST ELECTRI | | | INSPECTION !!!!! | | | 4) ALSO CUT SHEETS FOR FIXTURES. |
|