| Plan Review Notes For Permit 99090252 |
| Permit Number |
99090252 |
|
| Review Stop |
P |
| Sequence Number |
9 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1)SUBMIT DETAILED FLOOR PLAN OF TOILET | | | ROOM ON FIRST FLOOR.TOILET ROOM SHALL | | | COMPLY W/FACBC FOR ALL HANDICAP REQS. | | | SHOW LOCATION OF REQD.DRINKING FOUNTAIN. | | | FOUNTAIN SHALL COMPLY W/FACBC SEC. | | | 4.1.3(10)(A).PROVISIONS SHALL BE MADE | | | FOR PEOPLE WHO HAVE TROUBLE BENDING AND | | | STOOPING. | | | | | | 2)SHT.P202-CLARIFY "HWC"IN TOILET ROOM. | | | | | | 3)SHT.P206-A DRAIN IS REQD.ON THE WATER | | | HEATER PAN.TERMINATION OF DRAIN SHALL | | | COMPLY W/SPC SEC.507.8.3.DRAIN SHALL BE | | | A MIN.OF 1". | | | | | | 4)SHT.P207-RISER #3-SHOW SQ.FT.AREA | | | DRAINED BY EACH CANOPY DRAIN.COMPLY W/ | | | SPC SEC.1108.1 AND TABLE 1108.1. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | QUESTIONS. | | | | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|