| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SHOW ALL AIC RATINGS FOR | | | ALL EQUIPMENT BEING SHOWN. ALL MAINS/ | | | PANELS/BREAKERS MUST BE RATED FOR | | | AVAILABLE FAULT CURRENT. PER 110-9 | | | PLEASE SUBMIT ALL THE ABOVE PER 215-5 | | | | | | 2)NOTE: PLEASE NOTE THAT NOT ALL PANEL | | | SCHEDULES WERE SHOWN?? PLEASE DO SO. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561-659-8096 EXT 8372 |
|