| Date |
Text |
| 2001-01-08 00:00:00 | SUBMIT TOTAL OCCUPANT LOAD OF STRUCTURE |
| | PER SPC SEC.407.1.3. |
| | |
| | CONFIGURATION OF WOMEN'S RESTROOM ON SHT |
| | A1.5.DOESN'T CORRELATE W/SHTS.A1.2 OR |
| | A6.2.CLARIFY. |
| | |
| | CLEARLY SHOW LENGTH AND WIDTH DIMENSIONS |
| | OF HANDICAP STALLS AND TOILET ROOMS. |
| | COMPLY W/FACBC SEC.4.17.3 EXCEPTION:NEW |
| | CONSTRUCTION AND FIGURES 28 AND 30. |
| | |
| | GRAB BARS BEHIND WATER CLOSETS SHALL |
| | COMPLY W/FACBC SEC.4.16.4 & 4.17.6. |
| | |
| | CLEAR FLOOR SPACE UNDER HANDICAP LAVS. |
| | SHALL COMPLY W/FACBC SEC.4.19.2. |
| | |
| | SHOW MOUNTING HEIGHTS/DIMENSIONS OF ALL |
| | HANDICAP FIXTURES AND APPURTENANCES. |
| | COMPLY W/ALL APPLICABLE SECTIONS OF |
| | FACBC. |
| | |
| | DRINKING FOUNTAIN BY SECURITY OFFICE |
| | SHALL COMPLY W/FACBC SEC.4.1.3(10)(A) |
| | |
| | SUBMIT ISOMETRIC DRAWING FOR COMPLETE |
| | UNDERGROUND STORM DRAINAGE PIPING FOR |
| | THE BUILDING STORM DRAINAGE SYSTEM PER |
| | COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1 |
| | SIZING OF SYSTEM SHALL COMPLY W/SPC SEC. |
| | 1108.2.1.SYSTEM DOESN'T COMPLY. |
| | |
| | SUBMIT CALCULATIONS/DETAILS FOR |
| | PROVISIONS FOR SECONDARY DRAINAGE FOR |
| | ROOF STRUCTURE PER SPC SEC.1109.SUBMIT |
| | DETAILS OF SCUPPERS W/ALL DIMENSIONS. |
| | |
| | CLEARLY SHOW TERMINATION POINT OF STORM |
| | DRAINAGE SYSTEM.(SEE 8"RISERS AND CANOPY |
| | AT ROTUNDA ON A200.) |
| | |
| | SHT.P200-RISER #4 -4"ROOF DRAIN NOT |
| | SHOWN ON SHT.P206. |
| | |
| | SHT.P201-RISER FOR MSB ON 2ND FLR.DOES |
| | NOT CORRELATE W/ISOMETRIC ON P206.(SEE |
| | AREA AT COLS.9-10 BETWEEN E-F.) |
| | |
| | FLOOR DRAINS IN RESTROOMS AND FAMILY |
| | TOILET ROOM ARE S-TRAPPED.COMPLY W/SPC |
| | SEC.901.2. |
| | |
| | SHOW SIZE OF CONDENSATE DRAINS ON PLANS. |
| | COMPLY W/SMC SEC.304.8.4. |
| | |
| | SHT.P206.-2ND.FLR.MEN'S AND WOMEN'S R.R. |
| | SIZING OF DRAINAGE SYSTEM SHALL COMPLY |
| | W/SPC TABLE 714.2.(REFER TO 1 1/2"& 2" |
| | DRAINS). |
| | |
| | BRANCH VENT SIZING FOR WATER CLOSETS |
| | SHALL COMPLY W/SPC TABLE 902.2. |
| | |
| | SHT.P206-JANITOR SINK NOT SHOWN ON WATER |
| | AND SANITARY RISERS. |
| | |
| | SHT.P201 REFERS TO SHT.P700 FOR CONTIN- |
| | UATION OF SANITARY.NO SUCH SHEET IS IN |
| | PLANS. |
| | |
| | A HEATER PAN AND PAN DRAIN ARE REQUIRED |
| | FOR THE EWH.COMPLY W/COUNTYWIDE AMEND- |
| | MENTS TO SPC SEC.507.8.1. |
| | |
| | MAX.TEMPERATURE OF WATER TO PUBLIC REST- |
| | ROOMS SHALL BE 110 DEGREES PER FEC SEC. |
| | 412.1.ABCD.2.3.2. |
| | |
| | HOSE BIBBS SHALL BE VALVED PER SPC SEC. |
| | 610.4.1. |
| | |
| | SHT.P206-WATER SUPPLY CONTROL SHALL |
| | COMPLY W/SPC SEC.610.4.1 & 610.4.2. |
| | |
| | VENTS THRU ROOF SHALL NOT BE INCREASED |
| | IN SIZE (ONLY WHERE FROST CLOSURE IS A |
| | PROBLEM.)SPC SEC.905.2,918,920.2.-SEE |
| | FUTURE RESTROOM AREA,& F.D.AT PUMP ROOM. |
| | |
| | THE FOLLOWING JOB SPECS.DO NOT COMPLY |
| | W/SPC.THEY SHALL BE CHANGED TO COMPLY |
| | W/THE FOLLOWING CODE SECS.: |
| | PAGE 15410-15-(H)(I)-VERT.AND HORIZONTAL |
| | SUPPORTS SHALL COMPLY W/SPC SEC.310.2- |
| | 310.3.6. |
| | PAGE 15430-6-(3.3)-CLEANOUTS SHALL |
| | COMPLY W/SPC 710.2.4. |
| | PAGE 15497(1-3)SECS.3.2-3.5-SYSTEM TESTS |
| | SHALL COMPLY W/SPC SECS.311.2-311.7.5. |