| Plan Review Notes For Permit 99090252 |
| Permit Number |
99090252 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ********CORRECTED BY LETTER ATTACHED**** | | | EXHAUST FANS ARE NOT ALL INDICATED ON | | | ROOF PROVIDE LOCATION FOR EACH FAN. | | | PROVIDE AIR BALANCE SCHEDULE PER 1997 | | | SMC 501.2 | | | PROVIDE OUTSIDE AIT CALCULATIONS PER | | | ASHRAE 62-89 | | | EXHAUST AIR TOTALS IN BUILDING DOES NOT | | | MATCH FAN CAPACITY ON SCHEDULE |
|