| 2001-01-08 00:00:00 | SUBMIT OCCUPANT LOAD PER SPC SEC.407.1.3 |
| | |
| | NUMBER OF DRINKING FOUNTAINS FOR |
| | OCCUPANT LOAD SHALL COMPLY W/TABLE 407 |
| | OF SPC. |
| | |
| | SUBMIT STORM DRAINAGE ISOMETRIC FOR |
| | REVIEW.COMPLY W/SPC SECS.1108. |
| | |
| | SUBMIT CALCULATIONS/DETAILS FOR |
| | PROVISIONS FOR SECONDARY DRAINAGE FOR |
| | ROOF STRUCTURE PER SPC SEC.1109. |
| | |
| | CONFIGURATION OF WOMEN'S RESTROOM ON |
| | A1.2 DOESN'T CORRELATE W/SHT.A1.5 OR |
| | A6.2.(AMOUNT OF PLBG.FIXTURES DOESN'T |
| | MATCH.) |
| | |
| | CLEARLY SHOW LENGTH AND WIDTH DIMENSIONS |
| | OF HANDICAP STALLS AND TOILET ROOM. |
| | COMPLY W/FACBC SEC.4.17.3 EXCEPTION:NEW |
| | CONSTRUCTION AND FIGURES 28 & 30. |
| | |
| | SHT.A6.2-GRAB BARS BEHIND WATER CLOSETS |
| | SHALL COMPLY W/FACBC SEC.4.16.4 & 4.17.6 |
| | |
| | CLEAR FLOOR SPACE UNDER HANDICAP LAV. |
| | SHALL COMPLY W/FACBC SEC.4.19.2. |
| | |
| | SHOW MOUNTING HEIGHTS/DIMENSIONS OF ALL |
| | HANDICAP FIXTURES AND APPURTENANCES. |
| | COMPLY W/FACBC. |
| | |
| | DISTANCE OF FLOOR DRAINS FROM VENT SHALL |
| | COMPLY W/TABLE 908.1 OF COUNTYWIDE |
| | AMENDMENTS TO STD.PLBG.CODE. |
| | |
| | SHT.P200-CLEARLY SHOW CONTINUATION POINT |
| | OF 8" STORM DRAIN AND SANITARY LINE.SEE |
| | COLS.#B-D & "10". |
| | |
| | SUBMIT A STORM DRAINAGE ISOMETRIC FOR |
| | REVIEW.NOTE SQUARE FOOTAGE DRAINED BY |
| | EACH ROOF DRAIN.COMPLY W/SPC SEC.1108.1, |
| | 1108.2. |
| | |
| | SHT.P201-RISER FOR MSB ON 2ND FLR. |
| | DOESN'T CORRELATE W/ISOMETRIC ON P206. |
| | SPC 104.2.1. |
| | |
| | FLOOR DRAINS ARE NOT PROPERLY VENTED PER |
| | SPC SEC.901.2 |
| | |
| | FLOOR DRAIN IS REQD.IN THE FAMILY TOILET |
| | ROOM PER SPC SEC.409.4.1.1. |
| | |
| | SHT.P206-CLEARLY SHOW ORIGINATION POINT |
| | OF DOMESTIC WATER LINE.SPC 104.2.1. |
| | A BACKFLOW DEVICE IS REQD.ON THE WATER |
| | SERVICE TO THE BLDG.PER SPC SEC.606. |
| | |
| | JOB SPECS.-PG.15410-15.-(H)(I)-VERTICAL |
| | AND HORIZ.SUPPORTS SHALL COMPLY W/SPC |
| | SEC.310.2-310.3.6. |
| | |
| | JOB SPECS.-PG.15430-6.-(3.3)-CLEANOUTS |
| | SHALL COMPLY W/SPC 710.2.4. |
| | |
| | JOB SPECS.-PG.15497-SECS.3.2-3.5.SYSTEM |
| | TESTS SHALL COMPLY W/SPC SECS.311.2 - |
| | 311.7.5. |
| | |
| | *************SHELL ONLY***************** |
| | |
| | SUBMIT ISOMETRIC DRAWINGS FOR ALL WATER, |
| | SANITARY,STORM AND CONDENSATE SYSTEMS TO |
| | BE INSTALLED IN THE SHELL STRUCTURE. . |
| | SPC 104.2.1. |
| | |
| | ROOF SYSTEM SHALL BE SUPPLIED W/ |
| | PROVISIONS FOR SECONDARY DRAINAGE PER |
| | SPC SEC.1109. |
| | |
| | CLEARLY SHOW ORIGINATION /TERMINATION |
| | POINTS OF THE SANITARY,STORM,CONDENSATE, |
| | AND WATER SYSTEMS ON THE PLANS.SPC 104.2 |
| | |
| | A BACKFLOW PREVENTION DEVICE IS REQD.ON |
| | THE DOMESTIC WATER SYSTEM PER SPC SEC. |
| | 606. |
| | |
| | NOTE:PLUMBING PROVISO: |
| | THE ABOVE INFORMATION FOR THE SHELL BLDG |
| | SHALL BE SUBMITTED FOR REVIEW WITHIN |
| | 30 DAYS OF ISSUANCE OF SHELL PERMIT. |
| | 10/4/99.T.LARGE. |