| Plan Review Notes For Permit 99090234 |
| Permit Number |
99090234 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | SUBMIT SANITARY AND WATER ISOMETRICS | | | FOR THE CHANGES TO THE PLBG.SYSTEM PER | | | SPC 104.2.1. | | | | | | CLEARLY SHOW DIMENSIONS OF TOILET ROOM | | | IN LAB.COMPLY W/SPC SEC.403.4. | | | | | | SINK IN KITCHEN SHALL COMPLY W/FACBC | | | SECS.4.24.1 - 4.24.7. | | | | | | SUBMIT DETAILS FOR HANDICAP FIXTURES. | | | COMPLY W/FACBC FOR ALL REQS. | | | | | | FLOOR DRAIN REQD.IN TOILET ROOM.SPC | | | 409.4.1.1. | | | | | | WALLS AND FLOOR IN NEW TOILET ROOM TO BE | | | NON-ABSORBENT TO 4' PER SBC SEC.1204.2. |
|