| 2001-01-08 00:00:00 | SUBMIT OCCUPANT LOAD FOR EACH LEVEL AND |
| | TOTAL OCCUPANT LOAD TO ENSURE COMPLIANCE |
| | W/TABLE 407 AND FLA.STATUTE 553.141 |
| | (POTTY PARITY)FOR M,IN.FIXTURE REQS. |
| | |
| | DRINKING FOUNTAINS ARE REQD.PER TABLE |
| | 407 OF SPC.DRINKING FOUNTAINS SHALL |
| | COMPLY W/FACBC SECS.4.1.3(10)(A),4.15. |
| | |
| | TOILET STALLS SHALL COMPLY W/FACBC SECS. |
| | 4.17,4.17.3(SEE EXCEPTION:NEW |
| | CONSTRUCTION)A LAVATORY IS REQD.IN THE |
| | ACCESSIBLE STALL. |
| | |
| | SUBMIT COMPLETE DETAILS FOR HANDICAP |
| | FIXTURES AND ACCESSORIES.COMPLY W/FACBC |
| | REQS. |
| | |
| | SUBMIT A WATER,SANITARY,STORM AND COND. |
| | ISOMETRIC FOR REVIEW.SPC 104.2.1. |
| | |
| | PLBG.SHEETS REFER TO CIVIL DRWGS.FOR |
| | CONTINUATION OF PLBG.LINES.SUBMIT CIVIL |
| | DRWGS.FOR REVIEW.104.2.1. |
| | |
| | PLANS SHALL BE REVIEWED AND APPROVED BY |
| | PALM BEACH COUNTY HEALTH DEPT.PRIOR TO |
| | REVIEW BY THIS DEPT.SPC SEC.101.4.7. |
| | |
| | A BACKFLOW DEVICE IS REQD.ON THE |
| | DOMESTIC WATER SERVICE PER SPCSEC.606. |
| | |
| | WALLS AND FLOORS IN RESTROOMS AND TOILET |
| | ROOMS SHALL COMPLY W/SBC SEC.1204.2. |
| | |
| | FLOOR DRAINS ARE REQD.IN RESTROOMS AND |
| | TOILET ROOMS PER SPC SEC.409.4.4.1. |
| | |
| | PROVISIONS FOR DRAINAGE OF OVERFLOW |
| | WATER FROM THE ROOF STRUCTURE SHALL BE |
| | PROVIDED PER SBC SEC.1517.6.4.1.THRU |
| | 1517.6.4.3.,1604.6.2.SUBMIT SIZE AND |
| | DETAILS OF SCUPPERS/OVERFLOW DRAINAGE. |
| | |
| | CONTACT RODNEY COMPO FOR INFORMATION |
| | REGARDING GREASE INTERCEPTOR AT CITY OF |
| | W.P.B.REGIONAL SEWER TREATMENT PLANT AT |
| | 835-7423.SHOW DISTANCE OF GREASE INT. |
| | FROM BLDG.COMPLY W/SBC SEC.1803.1.3. |
| | |
| | SUBMIT DETAIL OF GREASE INT.SPC 104.2.1. |
| | 1004.2 |
| | |
| | NUMBER OF REQD.URINALS SHALL COMPLY |
| | W/SPC TABLE 407 FOOTNOTE #3. |
| | |
| | UNISEX TOILET ROOMS ARE ONLY PERMITTED |
| | AS ALLOWED IN TABLE 407 FOOTNOTE #6. |
| | |
| | |
| | AN ADDITIONAL TOILET STALL SHALL COMPLY |
| | W/FACBC SEC.4.22.4. |
| | |
| | *********COMMENTS FOR SHELL ONLY******* |
| | SUBMIT A WATER,SANITARY,STORM AND |
| | CONDENSATE ISOMETRIC FOR REVIEW.SPC |
| | SEC.104.2.1. |
| | |
| | PLANS REFER TO CIVIL DRWGS.FOR CONTIN- |
| | UATION OF PLBG. LINES.SUBMIT CIVIL DWGS. |
| | FOR REVIEW OR LIST PERMIT NUMBER FOR |
| | THIS WORK. |
| | |
| | A BACKFLOW PREVENTION DEVICE IS REQD.ON |
| | THE DOMESTIC WATER SERVICE PER SPC SEC. |
| | 606. |
| | |
| | PROVISIONS FOR DRAINAGE OF OVERFLOW |
| | WATER FROM THE ROOF STRUCTURE SHALL BE |
| | PROVIDED PER SBC SEC.1517.6.4.1 THRU |
| | 1517.6.4.3.,1604.6.2. SUBMIT SIZE AND |
| | DETAILS OF SCUPPERS/OVERFLOW DRAINAGE. |
| | |
| | CONTACT RODNEY COMPO FOR INFORMATION |
| | REGARDING GREASE INTERCEPTOR SIZE AT |
| | CITY OF W.P.B. REGIONAL SEWER TREATMENT |
| | PLANT AT (561)835-7423.SHOW DISTANCE OF |
| | GREASE INTERCEPTOR FROM BLDG.COMPLY W/ |
| | SBC SEC.1803.1.3. |
| | |
| | SUBMIT DETAIL OF GREASE INTERCEPTOR. |
| | SPC SEC.104.2.1. |