| Plan Review Notes For Permit 99090087 |
| Permit Number |
99090087 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************PROVISO******************** | | | | | | 1)NOTE:NO EQUIPMENT GROUND FROM METER | | | THE FIRST MEANS OF DISC. | | | 2)NOTE:AS PER ART;250-81 GROUNDING | | | ELECTRODE CONDUCTOR TO BLDG.STEEL ALSO. | | | 3)NOTE:PANEL SCHEDULE TO SHOW BATH | | | CIRCUT. | | | 4)NOTE:AS PER ART;210-63 RECEPT.REQ`D | | | FOR A/C COND.UNIT. | | | 5)NOTE:NEED TO HAVE AIC RATING LISTED ON | | | PANELSCHED/RISER DIAGRAM AS PER ART; | | | 110-9, 215-5 | | | | | | | | | NEED TO SUBMIT THE ABOVE BEFORE THE | | | FIRST ROUGH ELECTRICAL INSPECTION. |
|