Plan Review Notes
Plan Review Notes For Permit 99090078
Permit Number 99090078
Review Stop R
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00REVISION:
 ROYAL WALL INSTEAD OF MASONRY:
  
 CHECKLIST:
 1-FIRE RATED WALL DOESN'T MEET THE
 REQUIREMENTS FOR SECTIONS 709.2.1.4.4
 AND 709.2.1.4.5 SBC 1997.
 (CALCULATIONS ARE INCORRECT).
 2-WHEN WALL FINISHES CONTRIBUTE TO GET
 THE TOTAL FIRE RESISTANCE OF THE WALL,
 THEN, THEY SHALL BE INSTALLED AS PER
 SECTION 709.3.1.6 SBC 1997.
 3-PROVIDE COMPLETE DETAILS AND SPECS
 FOR CONCRETE PANELS WITH ROUND AND
 ARCHED OPENINGS. SECTION 104.2.2 CITY
 AMENDMENTS TO SBC 1997.
 4-PROVIDE INFORMATION SHOWING THE R
 VALUE (12.9) CALCULATED IN THE ENERGY
 CALCULATIONS.SEC 104.2.2 CITY AMENDMEN
 5-PROVIDE COPIES OF APPROVED DRAWINGS
 REFERENCED ON THE PRODUCT APPROVAL.
 6-PROVIDE COMPLETE DETAILS AND SPECS FOR
 COLUMN AT REAR PORCH.
 SECTION 104.2.2 CITY AMENDMENTS.
  
 FROM PREVIOUS PROVISO:
 1-UPDATE ALL ENGINEERED TRUSSES.
 CUT AND PASTE IS NOT ACCEPTABLE.
 2-STORM PANELS:
 -PROVIDE A COMPLETE INSTALLATION
 SCHEDULE AS PER CITY SAMPLE.
 -PROVIDE DETAIL FOR INSTALLATION OF
 STORM PANELS AT FRONT WINDOWS. SEE
 EXTERIOR SILL DETAIL AND INSTALLATION
 SCHEDULE.
 3-PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOORS, WINDOW AT DINING AREA.