Plan Review Notes
Plan Review Notes For Permit 99090078
Permit Number 99090078
Review Stop R
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-PLEASE REVISE ALL ORIGINALS SHOWING
 ALL CLARIFICATIONS/CORRECTIONS MARKED
 ON SUBMITTED DRAWINGS.
 2-PROVIDE SAFETY GLASS IN LIBRARY WINDOW
 SEC. 2405.2 SBC 1997
 3-PROVIDE SPECIFICATIONS OF HOW TO
 COMPLY WITH SEC. 402.7.2 SGC 1997 FOR
 INSTALLATION OF GAS APPLIANCES IN THE
 GARAGE.
 4-ENTRY DOOR TO HAVE 32" MINIMUM CLEAR
 OPENING. TABLE 1004 SBC 1997.
 5-PROVIDE TWO COPIES OF ENGINEERED ROOF
 TRUSSES SIGNED AND SEALED AND REVIEWED
 BY DESIGNER OF RECORD.
 6-REVISE DESIGN CERITIFICATION FOR WIND
 LOAD COMPLIANCE FORM. MEAN ROOF HEIGHT
 IS 21"-0" MORE OR LESS.
 7-SPECIFY SIZE OF CEILING FANS. TABLE
 6-6 FLORIDA ENERGY CODE 1997 EDITION.
 CREDIT FOR CEILING FANS WAS TAKEN ON
 ENERGY CALCULATIONS.
 8-PROVIDE PRODUCT APPROVAL FOR WINDOW AT
 DINING AREA. CLARIFY IF WINDOW AT
 LIVING AREA HAS TRUE VERTICAL MULLIONS
 OR FALSE MULLIONS IN ORDER TO VERIFY
 SIZE OF FIXED WINDOW.
 9-STORM PANELS: PROVIDE A COMPLETE
 INSTALLATION SCHEDULE (AS PER CITY
 SAMPLE) AND KEY PLAN.
 10-PROVIDE ATTIC ACCESS TO MAIN ROOF.
 SEC 2309.6 SBC 1997.