| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************PROVISO****************** | | | | | | 1)NOTE: NEED TO SUBMIT AIC RATING OF | | | EQUIPMENT FIGURED FROM FAULT CURRENT | | | CALCULATIONS AS PER ARTS 110-9/215-5. | | | 2)NOTE:AS PER ART: 210-8-A-6 ALL OUTLETS | | | SERVING KITCHEN COUNTER SPACE ARE TO BE | | | GFI/GFI PROTECTED. | | | 3)NOTE:AS PER ART: 250-81 GROUNDING | | | ELECTRODE CONDUCTOR REQ`D TO GO TO BLDG. | | | STEEL ALSO. | | | 4)NOTE; NOTE ON RISER DIAGRAM,EQUIPMENT | | | GROUND ONLY AFTER FIRST MEANS OF DISC. | | | 5)NOTE:GFI FOR OPT.WHIRLPOOL TUB AND IS | | | TO BE ACCESSIBLE. | | | | | | NEED TO HAVE THE ABOVE INFORMATION | | | SUBMITTED AND APPROVED BEFORE ROUGH | | | ELECTRICAL INSPECTION. |
|