Plan Review Notes For Permit 99090078
Permit Number 99090078
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************PROVISO******************
  
 1)NOTE: NEED TO SUBMIT AIC RATING OF
 EQUIPMENT FIGURED FROM FAULT CURRENT
 CALCULATIONS AS PER ARTS 110-9/215-5.
 2)NOTE:AS PER ART: 210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTER SPACE ARE TO BE
 GFI/GFI PROTECTED.
 3)NOTE:AS PER ART: 250-81 GROUNDING
 ELECTRODE CONDUCTOR REQ`D TO GO TO BLDG.
 STEEL ALSO.
 4)NOTE; NOTE ON RISER DIAGRAM,EQUIPMENT
 GROUND ONLY AFTER FIRST MEANS OF DISC.
 5)NOTE:GFI FOR OPT.WHIRLPOOL TUB AND IS
 TO BE ACCESSIBLE.
  
 NEED TO HAVE THE ABOVE INFORMATION
 SUBMITTED AND APPROVED BEFORE ROUGH
 ELECTRICAL INSPECTION.