| Plan Review Notes For Permit 99090004 |
| Permit Number |
99090004 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************PROVISO****************** | | | | | | 1)NOTE;AS PER ARTS:110-9/215-5 NEED TO | | | SUBMIT AIC RATING FIGURED FROM FAULT | | | CURRENT CALCULATIONS. | | | 2)NOTE;AS PER 1996 NFPA-72 SMOKE | | | DETECTORS ARE REQ`D INSIDE AND OUTSIDE | | | ALL SLEEPING ROOMS IN NEW CONSTRUCTION | | | OF DWELLING UNITS. | | | 3)NOTE:AS PER ART;210-9-A-6 ALL OUTLETS | | | SERVING KITCHEN COUNTERTOPS ARE TO BE | | | GFI/GFI PROTECTED. | | | 4)NOTE:AS PER ART;210-52 2`6`12` RULE | | | APPLIES TO ALL WALL SPACE. | | | 5)NOTE:AS PER ART;250-81 GROUNDING | | | ELECTRODE CONDUCTOR IS TO GOT TO BLDG, | | | STEEL ALSO. | | | | | | ALL THE ABOVE NEEDS TO BE SUBMITTED | | | AND APPROVED BEFORE ROUGH ELECTRICAL | | | INSPECTION. |
|