Plan Review Notes
Plan Review Notes For Permit 99090004
Permit Number 99090004
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************PROVISO******************
  
 1)NOTE;AS PER ARTS:110-9/215-5 NEED TO
 SUBMIT AIC RATING FIGURED FROM FAULT
 CURRENT CALCULATIONS.
 2)NOTE;AS PER 1996 NFPA-72 SMOKE
 DETECTORS ARE REQ`D INSIDE AND OUTSIDE
 ALL SLEEPING ROOMS IN NEW CONSTRUCTION
 OF DWELLING UNITS.
 3)NOTE:AS PER ART;210-9-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTERTOPS ARE TO BE
 GFI/GFI PROTECTED.
 4)NOTE:AS PER ART;210-52 2`6`12` RULE
 APPLIES TO ALL WALL SPACE.
 5)NOTE:AS PER ART;250-81 GROUNDING
 ELECTRODE CONDUCTOR IS TO GOT TO BLDG,
 STEEL ALSO.
  
 ALL THE ABOVE NEEDS TO BE SUBMITTED
 AND APPROVED BEFORE ROUGH ELECTRICAL
 INSPECTION.