| Plan Review Notes For Permit 99081334 |
| Permit Number |
99081334 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | CONTACT RODNEY COMPO AT CITY OF WEST | | | PALM BEACH REGIONAL WASTEWWATER | | | TREATMENT PLANT REGARDING SIZE OF GREASE | | | INTERCEPTORS AT (561)835-7423. | | | | | | SHT.D-A8.03.-SUBMIT DETAILS ON SUMP PUMP | | | AND PIPING.SHOW TERMINATION POINT OF | | | DISCHARGE.COMPLY W/SPC SEC.717. | | | SHELL/FOUNDATION PLUMB. NOT REQUIRED | | | SUBMIT DETAIL OF GREASE INTERCEPTOR.SPC | | | 1004.2. | | | | | | INDICATE SLOPE OF PIPE FOR SANITARY | | | AND STORM SYSTEMS.COMPLY W/SPC SEC.705.1 | | | 705.2,TABLE 1108.1,1108.2. | | | | | | SUBMIT ISOMETRICS FOR THE SANITARY,STORM | | | CONDENSATE AND WATER SYSTEMS.SPC 104.2.1 | | | | | | CLEARLY IDENTIFY/LABEL MATCH LINES AND | | | COLUMN LINES FOR REVIEW PROCESS.SPC | | | 104.2.1. | | | | | | SUBMIT OVERALL DIMENSIONS OF FLAT ROOF | | | BEING DRAINED TO DETERMINE COMPLIANCE | | | W/SPC SEC.1108. | | | | | | PLBG.PROVISO:NO PLBG.-FOUNDATION PERMIT | | | ONLY.11/1/99. |
|