Plan Review Notes
Plan Review Notes For Permit 99081334
Permit Number 99081334
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00PROVISO:
 1)M3.01 SHAFT BY STAIRWELL #1 NEEDS FIRE
 DAMPER AT 12" X 12" EXH DUCT
 2)M3.06 FIRE DAMPERS REQUIRED AT PENETRA
 TION OF STAIRWELL WALL BY 12X12 EXH DUCT
 AND 16X 16 TE DUCT
 3)M3.06 FIRE DAMPERS REQUIRED AT PENETRA
 TION OF TRASH ROOM WALL BY 2 EXDUCTS