| 2001-01-08 00:00:00 | ************DENIED********************** |
| | |
| | 1)NOTE:SERVICE ENTRANCE CONDUCTORS NEED |
| | TO BE SIZED FOR ATLEAST THE LOAD OF THE |
| | SERVICE!!!!!! |
| | 2)NOTE:PLEASE REVISE LOAD CALCULATION |
| | COMBINING BOTH PANELS FOR SERVICE |
| | CALCULATION. |
| | 3)NOTE:RISER ONLY SHOWS 4/0 WHICH IS |
| | RATED FOR 230 AMPS AND CAN BE PROTECTED |
| | AT 250A BUT THE LOAD EXCEEDS THAT RATING |
| | OF THE WIRE.AS PER 310-16!!!!! |
| | SIZE SERVICE ENTRANCE CONDUCTORS ACCORD. |
| | 4)NOTE:PLANS SHOW 2 WATER HEATERS AND |
| | 2 DRYERS???? PANEL SCHEDULES AND LOAD |
| | CALCULATIONS ONLY SHOW ONE OF EACH |
| | BEING FIGURED???? PLEASE VERIFY!!! |
| | 5)NOTE: PLEASE ADD CIRCUT(S) ON PANEL |
| | SCHD.THAT ARE REQ`D BY 210-52D FOR BATHS |
| | 6)NOTE:NEED TO HAVE GROUNDING ELECTRODE |
| | CONDUCTOR GOING TO STEEL OF NEW |
| | STRUCTURES.AS PER 250-81 |
| | 7)NOTE:AT DETACHED STRUCTURE BACK YARD,, |
| | IF FED BY MORE THAN ONE BRANCH CIRCUT |
| | THEN MUST MEET CODE AS TO PROPER GROUND- |
| | -ING. AS PER 250-24 C-3 |
| | 8)NOTE:ON PLANS,,,SHEET 5 OF 15 SHOW |
| | 4 A/C COND. UNITS AND 9 OF 15 SHOW ONLY |
| | 2 A/C COND. UNITS??? ALSO PLANS 3 AHU`S |
| | ??WHAT ARE THE CORRECT AMOUNT OF UNITS?? |
| | 9)NOTE:AS REQ`D BY ART;210-8-A-6 ALL |
| | OUTLETS SERVING KITCHEN COUNTERSPACE ARE |
| | TO BE GFI/GFI PROTECTED. PLEASE LABEL. |
| | 10)NOTE:PLEASE NOTE SOME MISSING OUTLETS |
| | THAT ARE REQ`D BY 210-52 |
| | 11)NOTE:NEED TO SUBMIT THE AIC RATING OF |
| | EQUIPMENT MAINS AND BRKRS.AIC RATING IS |
| | IGURED FROM FAULT CURRENT CALCULATIONS. |
| | AS REQ`D BY 110-9/10 AND 215-5 |
| | NOTE ALL THE ABOVE SERVICE INFORMATION |
| | REQ`D BY 215-5 |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFORNATION |
| | REQ`STED FOR REVIEW AND APPROVAL!! |
| | ELEC WILL NOT PRINT |