| Plan Review Notes For Permit 99081314 |
| Permit Number |
99081314 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ****************DENIED****************** | | | | | | 1)NOTE:AS PER ART210-8-A-6 ALL RECEPTS. | | | SERVING KITCHEN COUNTER SPACE ARE TO BE | | | GFI/GFI PROTECTED, TO INCLUDE KITCHEN | | | AREA. | | | 2)NOTE;IF DETACHED CABANA HAS NORE THAN | | | ONE CIRCUT TO THAT STUCTURE,THEN IT REQ` | | | S A MEANS OF DISC. ST THAT STRUCTURE. | | | 3)AS PER 310-16 SERVICE ENTRANCE CONDS. | | | ARE NOT OF SUFFICENT SIZE.LOAD CALCS. | | | SHOW LOAD ON PANEL'A' AT 186.22 AND LOAD | | | ON PANEL'B'AT 80.54 THATS 266.76 ON 4/0 | | | WIRE WHICH IS ONLY RATED FOR 230AMPS!!! | | | SIZE CONDUCTORS AS PER 310-16 TO GUTTER | | | TAPS MAY BE SIZED TO PANEL RATING. | | | 4)NOTE:AS PER ARTS;110-9/215-5 NEED TO | | | SUBMIT AIC RATING OF ALL EQUIPMENT | | | BEING USED TO INCLUDE AIC RATING OF | | | MAINS, | | | 5)NOTE;SIZE GUTTER TO NEW SERVICE | | | CONDUCTORS | | | 6)NOTE;SIZE GROUNDING ELECTRODE COND- | | | -UCTOR TO NEW SERVICE ENTRANCE CONDUCTOR | | | 7)NOTE;AS PER ART 250-81,GROUNDING ELEC- | | | -TRODE CONDUCTOR TO GOT TO TO BLDG. | | | STEEL OF NEW ADDITIONS. | | | | | | NEED TO SUBMIT THE ABOVE INFORMATION | | | FOR APPROVAL. |
|