Plan Review Notes
Plan Review Notes For Permit 99081302
Permit Number 99081302
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00SUBMIT WATER RISER FOR REVIEW THAT
 CLEARLY REFLECTS THE ENTIRE SCOPE OF
 WORK BEING PERFORMED.WATER SUPPLY
 CONTROL SHALL COMPLY W/SPC SEC.610.4.1,
 610.4.2.
  
 MIN.SIZE WASTE STACK FOR URINAL SHALL BE
 2"PER SPC SEC.1003.2.
  
 MIN. SIZE OF SANITARY LINE U/G SHALL BE
 2" PER SPC SEC.714.4.
  
 HANDICAP ACCESSIBLE WATER FOUNTAIN SHALL
 COMPLY W/FACBC SEC.4.1.3(10)(A).