2001-01-08 00:00:00SECOND CHECKLIST:
 1-PAY IMPACT FEES TO THE COUNTY.
 2-ARCHITECT'S NAME WAS CROSSED OUT AND
 THERE IS NOT LETTER OF ARCHITECT
 REGARDING SUCH ACTION.
 ALSO, NEED TO REPRINT DRAWINGS WITHOUT
 THE COPYRIGHT STATEMENT.
 3-DELETE THE OPTIONAL PORCH FROM
 ORIGINAL DRAWINGS.
 4-PROVIDE THE DESIGN PRESSURES FOR ALL
 EXTERIOR OPENINGS. SEC. 1606 SBC 1997.
 5-PROVIDE PRODUCT APPROVALS FOR:
 BUTT GLAZING ASSEMBLY, FIREPLACE,
 WINDOW AND DOOR MULLIONS, ENTRY DOOR
 WITH TRANSOM ABOVE ASSEMBLY, FIXED
 WINDOW AT FAMILY AND LIVING ROOM, ROOF
 TILE, CURRENT SLIDING GLASS DOORS
 PRODUCT APPROVAL.
 6-PROVIDE SPECIFICATIONS OF HOW TO
 COMPLY WITH SEC. 402.7 SGC 1997 FOR
 INSTALLATION OF GAS APPLIANCES IN THE
 GARAGE.
 7-PROVIDE COMPLETE INSTALLATION DETAILS
 FOR AHU'S IN ATTIC. SEC 104.2.2 CITY
 AMENDMENTS TO SBC 1997.
 8-PROVIDE COMPLETE INSTALLATION DETAILS
 AND SPECIFICATIONS FOR CONSTRUCTION
 BETWEEN WINDOWS AT FRON ELEVATION OF
 THE HOUSE. SEC. 104.2.2 CITY AMENDMENTS
 9-PROVIDE ATTIC ACCESS.SEC 2309.6 SBC/97
 10-PROVIDE COMPLETE DETAILS AND SPECS
 FOR CONSTRUCTION OF CHIMNEY.
 SEC. 104.2.2 CITY AMENDMENTS.
 11-PROVIDE COMPLETE COLUMN SCHEDULE.
 SEC. 104.2.2 CITY AMENDMENTS.
 12-PROVIDE COMPLETE DETAILS AND SPECS
 FOR FRONT AND REAR PORCHES' CEILING
 CONSTRUCTION. SEC 2504.2 SBC 1997.
 13-SHEET S-2. REVISE DESIGN LOADS AS
 REQUIRED. SEE APPENDIX A OF SBC 1997.
 ALSO, REVISE DESIGN CERTIFICATION FOR
 WIND LOAD COMPLIANCE FORM. MEAN ROOF
 HEIGHT AND DESIGN PRESSURE DON'T MATCH.
 SEE TABLE 1606.2A SBC 1997.
 14-SPECIFY SIZE OF CEILING FANS AS PER
 TABLE 6-6 OF FLORIDA ENERGY CODE, 1997.
 CREDIT IS TAKEN IN ENERGY CALCULATIONS
 FOR CEILING FANS.
 15-FOOTING F2 IS ENCROACHING INTO THE
 NEIGHBOR'S PROPERTY AT ZERO LOT LINE.
 16-STORM PANELS:
 *REVISE INSTALLATION SCHEDULE.
 EG: OPENINGS #1,2,6,7, ETC.
 *REVISE ANCHOR SCHEDULE AS REQUIRED.
 NOT ALL THE STRUTURE IS 3000 PSI CONC.
 SOME AREAS THERE IS CONCRETE BLOCK.
 *PROVIDE DETAIL SHOWING INSTALLATION OF
 STORM PANEL AT FRONT WINDOWS WHERE
 THERE MAY A CONFLICT WITH ELABORATED
 TRIM AROUND THE WINDOWS.
 17-PROVIDE COMPLETE SPECIFICATIONS AND
 DETAILS FOR INSTALLATION OF BUTT
 GLAZING. SEC 104.2.2 CITY AMENDMENTS.
 18-PROVIDE TWO COPIES OF ENGINEERED
 TRUSS DRAWINGS SIGNED AND SEALED AND
 REVIEWED BY THE DESIGNER OF RECORD.
 19-SEE PLANS FOR ADDITIONAL COMMENTS AND
 REVISE ALL ORIGINAL DRAWINGS SHOWING
 THE CLARIFICATIONS/CORRECTIONS AS
 REQUESTED.
 20-OWES $405.32 FOR LOW VALUATION AND
 RADON FEES.
  
 NOTE:
 PLEASE RETURN REVIEWED SET AFTER ALL
 CLARIFICATIONS/CORRECTIONS ARE DONE, IN
 ORDER TO EXPEDITE THE REVIEW PROCESS.