Plan Review Notes
Plan Review Notes For Permit 99081169
Permit Number 99081169
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*******************PROVISO**************
  
 1)NOTE:AS PER ARTS:110-9/215-5 NEED TO
 SUBMIT AIC RATING OF EQUIPMENT,MAINS AND
 BRKRS. AIC RATING IS FIGURED FRON FAULT
 CURRENT CALCULATIONS.
 2)NOTE;OUTLETS IN LAUNDRY ROOM AND
 GARAGE ARE REQ`D TO BE GFI/GFI PROTECTED
 3)NOTE:AS PER ART:210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED.
 4)NOTE:GROUNDING ELECTRODE CONDUCTOR IS
 REQ`D TO GO TO BLDG.STEEL ALSO.AS PER
 ART:250-81
 5)NOTE:OUTLET SPACING IS TO CONFORM TO
 ART:210-52 2`6`12` RULE.
  
 NEED TO SUBMIT FOR REVIEW AND APPROVAL
 BEFORE FIRST ROUGH ELECTRICAL INSPECTION