| Plan Review Notes For Permit 99081169 |
| Permit Number |
99081169 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *******************PROVISO************** | | | | | | 1)NOTE:AS PER ARTS:110-9/215-5 NEED TO | | | SUBMIT AIC RATING OF EQUIPMENT,MAINS AND | | | BRKRS. AIC RATING IS FIGURED FRON FAULT | | | CURRENT CALCULATIONS. | | | 2)NOTE;OUTLETS IN LAUNDRY ROOM AND | | | GARAGE ARE REQ`D TO BE GFI/GFI PROTECTED | | | 3)NOTE:AS PER ART:210-8-A-6 ALL OUTLETS | | | SERVING KITCHEN COUNTERSPACE ARE TO BE | | | GFI/GFI PROTECTED. | | | 4)NOTE:GROUNDING ELECTRODE CONDUCTOR IS | | | REQ`D TO GO TO BLDG.STEEL ALSO.AS PER | | | ART:250-81 | | | 5)NOTE:OUTLET SPACING IS TO CONFORM TO | | | ART:210-52 2`6`12` RULE. | | | | | | NEED TO SUBMIT FOR REVIEW AND APPROVAL | | | BEFORE FIRST ROUGH ELECTRICAL INSPECTION |
|