2001-01-08 00:00:00INDICATE SUPPLY PRESSURE ON PLAN AND
 DISTANCE OF METER FROM BLDG.PER STD.GAS
 CODE SEC.305.2.
  
 SHOW ALL CUT LENGTHS OF PIPE AND
 DISTANCE TO MOST REMOTE OUTLET IN BLDG.
 PER STD.GAS CODE SEC.305.4.
  
 INDICATE TYPE OF PIPING TO BE USED.
 COMPLY W/SGC SEC.COMPLY W/TABLES LISTED
 IN SGC SEC.305.4.
  
 SUBMIT CORRECT BTU LOAD ON SYSTEM.SGC
 SEC.305.3.1.