| Plan Review Notes For Permit 99081085 |
| Permit Number |
99081085 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | SUBMIT PROPER EHD OF CSST TUBING AND | | | COMPLY W/TABLE 305.4F OF SGC. | | | | | | A UNION SHALL BE INSTALLED DOWNSTREAM OF | | | S.O.V.TO PERMIT REMOVAL OF CONTROLS PER | | | NFPA 54 SEC.5.5.4. | | | | | | SIZE THE SUPPLY LINES TO THE RANGE,HOT | | | TOP RANGE AND FRYER.COMPLY W/SGC. |
|