Plan Review Notes
Plan Review Notes For Permit 99081019
Permit Number 99081019
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00***********PROVISO********************
  
 NOTE: NEED TO SUBMIT AIC RATING OF ALL
 EQUIPMENT PANELS,DISC, BREAKERS. NEED TO
 HAVE DRAWN ON PANEL SCHED. AS PER ARTS:
 110-9 AND 215-5
 NOTE: MASTER BEDROOM REQ`S SMOKE
 DETECTOR OUTSIDE AS PER NFPA-72
 2-2.1.1.1
 NOTE:ART 210-63 REQ`S GFI RECEPT. FOR
 A/C EQUIPMENT.
 NOTE:GRNDING ELECTRODE TO BLDG.STEEL,
 AND COLD WATER PIPE AS PER ART:250-81
  
 PLEASE HAVE SUBMITTED AND APPROVED
 BEFORE ROUGH ELECTRICAL INSPECTION.