| Plan Review Notes For Permit 99081017 |
| Permit Number |
99081017 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***************PROVISO****************** | | | | | | NOTE:NEED TO SUBMIT AIC RATING OF | | | EQUIPMENT, AND BRKRS. ART 110-9 215-5 | | | NOTE:SMOKE DETECTRORREQ`D OUTSIDE | | | MASTER BEDROOM AS PER NFPA-72 | | | NOTE:WP GFI REC. REQ`D FOR A/C 210-63 | | | NOTE: GROUNDING ELECTRODE CONDUCTOR | | | TO GO TO BLDG.STEEL AND COLD WATER PIPE. | | | | | | ALL THE ABOVE NEEDS TO BE DONE SUBMITTED | | | AND APPROVED BEFORE ROUGH ELECTRICAL | | | INSPECTION. |
|