| Plan Review Notes For Permit 99080937 |
| Permit Number |
99080937 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************PROVISO********************* | | | | | | 1)NOTE:AS PER ART;110-9/215-5 NEED TO | | | SUBMIT AIC RATING OF EQUIPMENT AND BRKS. | | | ABOVE FIGURED FROM FAULT CURRENT CALCS. | | | 2)NOTE:AS PER 1996 NFPA-72 2-2.1.1.1 | | | DETECTORS ARE REQ`D INSIDE AND OUTSIDE | | | ALL SLEEPING ROOMS. | | | 3)NOTE:AS PER ART; 250-81 GROUNDING | | | ELECTRODE CONDUCTOR IS REQ`D TO GO TO | | | BLDG.STEEL ALSO. | | | 4)NOTE;AS PER ART;210-8-A-6 ALL OUTLETS | | | SERVING KITCHEN COUNTER SPACE ARE TO BE | | | GFI/GFI PROTECTED. | | | 5)NOTE;OUTLET SPACING IS TO CONFORM TO | | | ART;210-52 2`6`12` RULE. | | | | | | NEED TO HAVE THE ABOVE SUBMITTED AND | | | APPROVED BEFORE FIRST ELECTRICAL | | | ROUGH INSPECTION. |
|