2001-01-08 00:00:00************PROVISO*********************
  
 1)NOTE:AS PER ART;110-9/215-5 NEED TO
 SUBMIT AIC RATING OF EQUIPMENT AND BRKS.
 ABOVE FIGURED FROM FAULT CURRENT CALCS.
 2)NOTE:AS PER 1996 NFPA-72 2-2.1.1.1
 DETECTORS ARE REQ`D INSIDE AND OUTSIDE
 ALL SLEEPING ROOMS.
 3)NOTE:AS PER ART; 250-81 GROUNDING
 ELECTRODE CONDUCTOR IS REQ`D TO GO TO
 BLDG.STEEL ALSO.
 4)NOTE;AS PER ART;210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTER SPACE ARE TO BE
 GFI/GFI PROTECTED.
 5)NOTE;OUTLET SPACING IS TO CONFORM TO
 ART;210-52 2`6`12` RULE.
  
 NEED TO HAVE THE ABOVE SUBMITTED AND
 APPROVED BEFORE FIRST ELECTRICAL
 ROUGH INSPECTION.