Plan Review Notes
Plan Review Notes For Permit 99080933
Permit Number 99080933
Review Stop E
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00************* UNSAT ******************
  
 1)NOTE:PLEASE NOTE THAT IN RISER DIAGRAM
 WHERE CONDUCTORS ARE BEING RUN IN PARA-
 -LLEL.THIS MEANS THERE MUST BE THE SAME
 AMOUNT AND SIZE CONDUCTORS IN EACH RISER
 2)NOTE: ALSO AS PER NEC ART;310-4 THE
 SMALLEST CONDUCTOR ALLOWED TO BE RUN IN
 PARALLEL IS 1/0.SUBMIT NEUTRAL CALC.!!
 3)NOTE:YOU SHOW #2 BEING FED TO PANELS
 C'AND 'A'. #2 IS NOT TO BE PROTECTED AT
 200 AMPS.! ALSO #2 IS TOO SMALL TO BE
 RUN IN PARALLEL 310-4.
 4)NOTE:PLEASE NOTE ,YOU SHOW EQUIPMENT
 GROUNDING CONDUCTOR GOING FROM METER TO
 DISCONNECT. ONLY AFTER FIRST MEANS OF
 DISC.
 5)NOTE:WIRE SIZE GOING TO PANEL 'D' IS
 TOO SMALL. 2/0 IS RATED FOR 175AMPS
 PER ART;310-16. LOAD YOU SHOW IS 180AMPS
 6)NOTE: STILL NEED TO SUBMIT NEUTRAL
 LOAD CALCULATION. 215-5
  
 PLEASE HAVE THE ABOVE CORRECTED AND
 SUBMITTED FOR REVIEW AND APPROVAL.
 IF THERE ANY QUESTIONS PLEASE CALL;
 561-659-8096 EXT 8372