| Plan Review Notes For Permit 99080933 |
| Permit Number |
99080933 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************* UNSAT ****************** | | | | | | 1)NOTE:PLEASE NOTE THAT IN RISER DIAGRAM | | | WHERE CONDUCTORS ARE BEING RUN IN PARA- | | | -LLEL.THIS MEANS THERE MUST BE THE SAME | | | AMOUNT AND SIZE CONDUCTORS IN EACH RISER | | | 2)NOTE: ALSO AS PER NEC ART;310-4 THE | | | SMALLEST CONDUCTOR ALLOWED TO BE RUN IN | | | PARALLEL IS 1/0.SUBMIT NEUTRAL CALC.!! | | | 3)NOTE:YOU SHOW #2 BEING FED TO PANELS | | | C'AND 'A'. #2 IS NOT TO BE PROTECTED AT | | | 200 AMPS.! ALSO #2 IS TOO SMALL TO BE | | | RUN IN PARALLEL 310-4. | | | 4)NOTE:PLEASE NOTE ,YOU SHOW EQUIPMENT | | | GROUNDING CONDUCTOR GOING FROM METER TO | | | DISCONNECT. ONLY AFTER FIRST MEANS OF | | | DISC. | | | 5)NOTE:WIRE SIZE GOING TO PANEL 'D' IS | | | TOO SMALL. 2/0 IS RATED FOR 175AMPS | | | PER ART;310-16. LOAD YOU SHOW IS 180AMPS | | | 6)NOTE: STILL NEED TO SUBMIT NEUTRAL | | | LOAD CALCULATION. 215-5 | | | | | | PLEASE HAVE THE ABOVE CORRECTED AND | | | SUBMITTED FOR REVIEW AND APPROVAL. | | | IF THERE ANY QUESTIONS PLEASE CALL; | | | 561-659-8096 EXT 8372 |
|