Plan Review Notes For Permit 99080933
Permit Number 99080933
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00INDICATE TYPE OF PIPING MATERIAL TO BE
 INSTALLED FOR GAS SYSTEM.COMPLY W/STD.
 GAS CODE SEC.306.
  
 SUBMIT MANUF.SHEETS FOR GAS EQUIPMENT.
 COMPLY W/STD.GAS CODE SEC.402.1.
  
 SUPPLY CALCULATIONS FOR COMBUSTION AIR
 FOR WATER HEATER AND DRYERS.COMPLY W/
 STD.GAS CODE SEC.402.4.
  
 SIZE ALL SECTIONS OF THE WATER RISER.NO
 MORE THAN 2 FIXTURES SHALL BE CONNECTED
 TO A 1/2" C.W. LINE AND 4 FIXTURES TO A
 H.W.LINE PER COUNTYWIDE AMENDMENTS SEC.
 607.7.
  
 A VENT IS REQD.ON THE FLOOR DRAIN FOR
 THE WASHING MACHINES PER SPC SEC.901.2.
  
 INDICATE SLOPE OF SANITARY SYSTEM AND
 NOTE FIXTURE LOAD PER SPC TABLE 713.1
 FOOTNOTE #3 AND NOTE SIZE OF STANDPIPE.
 SPC 1001.9.1.
  
 FLOOR DRAINS ARE REQD.IN THE TOILET
 ROOMS PER SPC 409.4.1.1.
  
 WALLS IN TOILET ROOMS SHALL BE NON-
 ABSORBENT MATERIAL TO 4' PER SBC SEC.
 1204.2
  
 DRINKING FOUNTAIN SHALL COMPLY W/FACBC
 SEC.4.1.3(10)(A).
  
 `