Date Text
2001-01-08 00:00:00 
  
 DENIED:
  
 1)PROVIDE CURRENT SURVEY SIGN AND SEALED
  
 2)PROVIDE ENERGY CALCULATIONS INCLUDING
 MANUEL J.
  
 3)PROVIDE COMPLETE DETAILS OF FLOOR
 TRUSS CONNECTION TO BEARING WALLS.
  
  
 4)PROVIDE COMPLETE ROOF AND SECOND FLOOR
 FRAMING PLAN.SPECIFY ALL CONNECTORS.
  
 5)PROVIDE COMPLETE THRU SECTION DETAILS
 OF STAIR CONSTRUCTION.
  
 6)PROVIDE DESIGN PRESSURES FOR ALL
 EXTERIOR OPENINGS.
  
 7)PROVIDE STORM PANEL INSTALLATION
 SCHEDULE AND KEY PLAN WITH SPECIFIC
 MOUNTING AND ANCHORS TO BE USED.
  
 8)PROVIDE ADDITIONAL COPIES OF LEGIBLE
 PRODUCT APPROVALS.
  
 SBC-1997 SEC 104.2