| Plan Review Notes For Permit 99080888 |
| Permit Number |
99080888 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | | | | | | | DENIED: | | | | | | 1)PROVIDE CURRENT SURVEY SIGN AND SEALED | | | | | | 2)PROVIDE ENERGY CALCULATIONS INCLUDING | | | MANUEL J. | | | | | | 3)PROVIDE COMPLETE DETAILS OF FLOOR | | | TRUSS CONNECTION TO BEARING WALLS. | | | | | | | | | 4)PROVIDE COMPLETE ROOF AND SECOND FLOOR | | | FRAMING PLAN.SPECIFY ALL CONNECTORS. | | | | | | 5)PROVIDE COMPLETE THRU SECTION DETAILS | | | OF STAIR CONSTRUCTION. | | | | | | 6)PROVIDE DESIGN PRESSURES FOR ALL | | | EXTERIOR OPENINGS. | | | | | | 7)PROVIDE STORM PANEL INSTALLATION | | | SCHEDULE AND KEY PLAN WITH SPECIFIC | | | MOUNTING AND ANCHORS TO BE USED. | | | | | | 8)PROVIDE ADDITIONAL COPIES OF LEGIBLE | | | PRODUCT APPROVALS. | | | | | | SBC-1997 SEC 104.2 |
|