Plan Review Notes
Plan Review Notes For Permit 99080888
Permit Number 99080888
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00SANITARY ISOMETRIC SHALL CORRELATE W/THE
 FLOOR PLAN.SPC 104.2.1.
  
 SIZE OF SHOWER SHALL COMPLY W/COUNTYWIDE
 AMENDMENTS TO STD.PLBG.CODE SEC.409.8.2.
 (MIN.1024 SQ.IN.AND 30"WIDE).
  
 PIPING EMBEDDED IN CONCRETE SHALL COMPLY
 W/SBC SECS.1907.3,1907.3.3- 1907.3.5.
 (SEE 3"STACK IN TIE BEAM).
  
 SUBMIT SANITARY ISOMETRIC FOR 2-STORY
 HOUSE.SUBMITTED ISOMETRIC IS FOR SINGLE
 STORY STRUCTURE.SPC 104.2.1.
  
 MIN.SIZE OF DRAINAGE PIPE UNDERGROUND
 SHALL BE 2" PER SPC SEC.714.4.