| Plan Review Notes For Permit 99080888 |
| Permit Number |
99080888 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************DENIED******************** | | | | | | 1)NOTE:AS PER ART;210-52G ALL RECEPTS. | | | IN GARAGE ARE TO BE GFI/GFI PROTECTED. | | | 2)NOTE: AS PER 210-52E RECEPTS.REQ`D | | | FRONT AND BACK OF DWELLING. | | | 3)NOTE:AS PER ART;210-70 LIVING ROOM | | | HAS MEANS OF EGRESS INTO GARAGE, LIGHT | | | SWITCH IS REQ`D NOTE 3-WAY. | | | 4)NOTE:AS PER ARTS;210-52C/210-8-A-6 | | | OUTLET SPACING IN KITCHEN ALONG | | | COUNTER SPACE AND ALL RECEPTS.IN KITCHEN | | | SERVING COUNTERSPACE ARE TO BE GFI/GFI | | | PROTECTED. | | | 5)NOTE:AS PER NFPA-96 SMOKE DETECTORS | | | ARE REQ`D INSDIE AND OUTSIDE ALL | | | SLEEPING ROOMS IN NEW CONSTUCTION HARD | | | WIRED 120V WITH BATTERY BACK-UP AND | | | WIRED IN LINE. | | | 6)NOTE:AS PER ART:210-52D BATH CIRCUTS | | | REQ` 20AMP DEDICATED CIRCUT.PLEASE LIST | | | ON PANEL SCHEDULE. | | | 7)NOTE:AS PER ART;250-81 GROUNDING | | | ELECTRODE CONDUCTOR IS REQ`D TO GO TO | | | BLDG.STEEL ALSO. | | | 8)NOTE:AS PER ARTS;110-9/215-5 MUST | | | HAVE AIC RATING OF ALL EQUIPMENT BEING | | | USED.PLEASE HAVE ON PANEL SCHED. | | | | | | PLEASE SUBMIT ALL THE ABOVE FOR APPROVAL |
|