Plan Review Notes
Plan Review Notes For Permit 99080888
Permit Number 99080888
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************DENIED********************
  
 1)NOTE:AS PER ART;210-52G ALL RECEPTS.
 IN GARAGE ARE TO BE GFI/GFI PROTECTED.
 2)NOTE: AS PER 210-52E RECEPTS.REQ`D
 FRONT AND BACK OF DWELLING.
 3)NOTE:AS PER ART;210-70 LIVING ROOM
 HAS MEANS OF EGRESS INTO GARAGE, LIGHT
 SWITCH IS REQ`D NOTE 3-WAY.
 4)NOTE:AS PER ARTS;210-52C/210-8-A-6
 OUTLET SPACING IN KITCHEN ALONG
 COUNTER SPACE AND ALL RECEPTS.IN KITCHEN
 SERVING COUNTERSPACE ARE TO BE GFI/GFI
 PROTECTED.
 5)NOTE:AS PER NFPA-96 SMOKE DETECTORS
 ARE REQ`D INSDIE AND OUTSIDE ALL
 SLEEPING ROOMS IN NEW CONSTUCTION HARD
 WIRED 120V WITH BATTERY BACK-UP AND
 WIRED IN LINE.
 6)NOTE:AS PER ART:210-52D BATH CIRCUTS
 REQ` 20AMP DEDICATED CIRCUT.PLEASE LIST
 ON PANEL SCHEDULE.
 7)NOTE:AS PER ART;250-81 GROUNDING
 ELECTRODE CONDUCTOR IS REQ`D TO GO TO
 BLDG.STEEL ALSO.
 8)NOTE:AS PER ARTS;110-9/215-5 MUST
 HAVE AIC RATING OF ALL EQUIPMENT BEING
 USED.PLEASE HAVE ON PANEL SCHED.
  
 PLEASE SUBMIT ALL THE ABOVE FOR APPROVAL