2001-01-08 00:00:00NDICATE SUPPLY PRESSURE AND TYPE OF
 PIPING USED FOR GAS SYSTEM.STD.GAS CODE
 SEC.305.4
  
 SUBMIT MANUF.SHEETS FOR ALL GAS EQUIP.
 STD.GAS CODE SEC.402.1.
  
 SUBMIT MANUF.SHEETS FOR GREASE RECOVERY
 UNIT.SPC 103.7, 104.2.1.
  
 SHOW SIZE OF EXIST. GASLINE.COMPLY W/
 STD.GAS CODE SEC.305.4(NOTE EXIST.BTU
 LOAD ON SYSTEM.
  
 CAN WASH SHALL DISCHARGE TO INTERCEPTOR.
 SPC SEC.1004.4.
  
 GREASE RECOVERY UNIT CANNOT BE LOCATED
 IN FOOD PREP.AREA PER DEPT. OF HEALTH.
  
 3-COMP.SINK NOT PROPERLY VENTED.COMPLY
 W/SPC SEC.901.2.
  
 SUBMIT OCCUPANT LOAD TO ENSURE
 COMPLIANCE W/SPC TABLE 407.