| Plan Review Notes For Permit 99080839 |
| Permit Number |
99080839 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | HORIZONTAL WET VENTS TO RECEIVE | | | DISCHARGE FROM FIXTURE DRAINS ONLY PER | | | COUNTYWIDE AMENDMENTS TO STD.PLBG.CODE | | | SEC.911.1.1 | | | | | | "M"COPPER NOT PERMITTED U/GPER | | | COUNTYWIDE AMENDMENTS TO STD.PLBG.CODE | | | SEC.611.3. | | | | | | INDICATE TYPE OF PIPE MATERIAL TO BE | | | USED FOR GAS SYSTEM. STD.GAS CODE SEC. | | | 302. | | | | | | SHOW LOCATION OF GAS METER AND INDICATE | | | SUPPLY PRESSURE OF SYSTEM ON PLANS. | | | SGC 305.2 | | | | | | WATER HEATER SHALL BE READILY ACCESSIBLE | | | PER SPC SEC.501.7.(PERMANENT LADDER REQD | | | OR HEATER SHALL BE INSTALLED ON FLOOR. | | | | | | SUBMIT OCCUPANT LOAD AND SQUARE FOOTAGE | | | OF BLDG.PER SBC 104.2.1.COMPLY W/TABLE | | | 407 OF SPC | | | | | | RESTROOMS SHALL COMPLY W/FLA.STATUTE | | | SEC.553.141.(EQUAL NUMBER OF FIXTURES | | | REQD.IN WOMANS AS IN MEN'S RESTROOM) | | | | | | PLANS SHALL BE ROUTED TO DEPT. OF BUS. | | | REGULATION PRIOR TO BEING REVIEWED BY | | | THIS DEPT.101.4.7. |
|