Plan Review Notes
Plan Review Notes For Permit 99080839
Permit Number 99080839
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00HORIZONTAL WET VENTS TO RECEIVE
 DISCHARGE FROM FIXTURE DRAINS ONLY PER
 COUNTYWIDE AMENDMENTS TO STD.PLBG.CODE
 SEC.911.1.1
  
 "M"COPPER NOT PERMITTED U/GPER
 COUNTYWIDE AMENDMENTS TO STD.PLBG.CODE
 SEC.611.3.
  
 INDICATE TYPE OF PIPE MATERIAL TO BE
 USED FOR GAS SYSTEM. STD.GAS CODE SEC.
 302.
  
 SHOW LOCATION OF GAS METER AND INDICATE
 SUPPLY PRESSURE OF SYSTEM ON PLANS.
 SGC 305.2
  
 WATER HEATER SHALL BE READILY ACCESSIBLE
 PER SPC SEC.501.7.(PERMANENT LADDER REQD
 OR HEATER SHALL BE INSTALLED ON FLOOR.
  
 SUBMIT OCCUPANT LOAD AND SQUARE FOOTAGE
 OF BLDG.PER SBC 104.2.1.COMPLY W/TABLE
 407 OF SPC
  
 RESTROOMS SHALL COMPLY W/FLA.STATUTE
 SEC.553.141.(EQUAL NUMBER OF FIXTURES
 REQD.IN WOMANS AS IN MEN'S RESTROOM)
  
 PLANS SHALL BE ROUTED TO DEPT. OF BUS.
 REGULATION PRIOR TO BEING REVIEWED BY
 THIS DEPT.101.4.7.