Plan Review Notes
Plan Review Notes For Permit 99080714
Permit Number 99080714
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00PLANS SHALL BE REVIEWED BY DEPT.OF
 BUSINESS REG.PRIOR TO REVIEW BY THIS
 DEPT.SPC SEC.101.4.7.
  
 SUBMIT MANUF.SHEETS FOR ALL GAS EQUIP.
 STD.GAS CODE SEC.402.1.
  
 SIZE ALL SECTIONS OF THE GAS RISER AND
 SHOW ALL CUT LENGTHS OF PIPE.STD.GAS
 CODE SEC.302,305.4
  
 INDICATE GAS SUPPLY PRESSURE ON PLANS
 PER STD.GAS CODE SEC.305.2.
  
 SUPPLY COMBUSTION AIR CALCULATIONS FOR
 ALL GAS EQUIPMENT.STD.GAS CODE SEC.402.4
  
 SIZE ALL INDIRECT WASTE LINES ON THE
 RISER.COMPLY W/SPC SEC.713.3,TABLE 713.2
  
 SHT.A-3.NOTE #11-"M" COPPER IS NOT
 PERMITTED FOR U/G USE PER COUNTYWIDE
 AMENDMENTS TO STD.PLBG.CODE SEC.611.3.
  
 PLANS SHALL BE SIGNED AND SEALED PER
 SPC SEC.104.2.3.
  
 SUBMIT SANITARY RISER FOR ANY PLBG.
 CHANGES TO THE RESTROOM.SPC 104.2.1.
  
 RESUBMIT 10-13-99 DENIED SEPERATE PREMIT
 FOR PLUMBING SEE NOTES ON SHT A-3
 END OF COMMENTS PES