| Plan Review Notes For Permit 99080714 |
| Permit Number |
99080714 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ****************PROVISO**************** | | | | | | 1)NOTE:EXISTING RISER DIAGRAM SHOWS | | | 3 PHASE EQUIPMENT AND ONLY SINGLE PHASE | | | WIRING.???? FROM MAIN TO PANEL. | | | 2)NOTE:IF PVC CONDUIT IS USED IN FEEDING | | | FROM PANEL "A" TO PANEL "B" THEN SIZE | | | EQUIPMENT GROUND SHALL BE SIZED FROM | | | TABLE:250-95 | | | 3)NOTE:RISER DIAGRAM SHOWS PANEL"B" AS | | | BEING INSTALLED AS NEW ? BUT PANEL | | | SCHEDULE SHOWS AS BEING EXISTING?? | | | IF PANEL "B" IS NEW THEN PROVIDE AIC | | | RATING OF BRANCH BREAKERS.AS PER ARTS: | | | 215-5/110-9 | | | | | | ALL THE ABOVE INFORMATION NEEDS TO BE | | | SUBMITTED FOR REVIEW AND APPROVAL BEFORE | | | FIRST ROUGH ELECTRICAL INSPECTION IS | | | CALLED IN. |
|