2001-01-08 00:00:00****************PROVISO****************
  
 1)NOTE:EXISTING RISER DIAGRAM SHOWS
 3 PHASE EQUIPMENT AND ONLY SINGLE PHASE
 WIRING.???? FROM MAIN TO PANEL.
 2)NOTE:IF PVC CONDUIT IS USED IN FEEDING
 FROM PANEL "A" TO PANEL "B" THEN SIZE
 EQUIPMENT GROUND SHALL BE SIZED FROM
 TABLE:250-95
 3)NOTE:RISER DIAGRAM SHOWS PANEL"B" AS
 BEING INSTALLED AS NEW ? BUT PANEL
 SCHEDULE SHOWS AS BEING EXISTING??
 IF PANEL "B" IS NEW THEN PROVIDE AIC
 RATING OF BRANCH BREAKERS.AS PER ARTS:
 215-5/110-9
  
 ALL THE ABOVE INFORMATION NEEDS TO BE
 SUBMITTED FOR REVIEW AND APPROVAL BEFORE
 FIRST ROUGH ELECTRICAL INSPECTION IS
 CALLED IN.