| Date |
Text |
| 2001-01-08 00:00:00 | CLEARLY SHOW WHEELCHAIR TURNING SPACE |
| | IN ACCESSIBLE TOILET ROOMS PER FACBC SEC |
| | 4.2.3 AND FIGURES 3A OR 3B. |
| | |
| | SINK IN BREAKROOM SHALL BE HANDICAP |
| | ACCESSIBLE PER FACBC SEC.4.24.1-4.24.7 |
| | |
| | SUBMIT DETAILS /ELEVATIONS FOR ALL |
| | HANDICAP ACCESSIBLE FIXTURES. |
| | COMPLY W/FACBC.SHOW FIXTURE CLEARANCES. |
| | |
| | DOOR IN MEN'S TOILET ROOM CANNOT SWING |
| | INTO CLEAR FLOOR SPACE FOR THE WATER |
| | CLOSET PER FACBC SEC.4.22.2. |
| | |
| | SUBMIT OCCUPANT LOAD PER TABLE 407 OF |
| | SPC. |
| | |
| | SUBMIT DETAILS ON TYPE OF OPERATIONS |
| | CONDUCTED IN WAREHOUSE.AN EMERGENCY |
| | SHOWER MAY BE REQD.PER SPC TABLE 407. |
| | |
| | SUBMIT A WATER RISER FOR REVIEW THAT |
| | CLEARLY REFLECTS THE SCOPE OF WORK BEING |
| | PERFORMED.SPC 104.2.1. |
| | |
| | SUBMIT DETAILS ON THE SUMP,DRAIN AND |
| | PUMPS IN THE TRUCKWELL AREA.SPC 104.2.1. |
| | |
| | INSTALLATION OF FIXTURES ON COMMON |
| | HORIZONTAL BRANCH SHAALL COMPLY W/SPC |
| | SEC.913.1.1,913.1.2. |
| | |
| | WET VENTS SHALL RECEIVE THE DISCHARGE |
| | OF FIXTURE DRAINS ONLY PER COUNTYWIDE |
| | AMENDMENTS SEC.911.1.1(MENS TOILET) |
| | |
| | DRINKING FOUNTAIN SHALL BE HANDICAP |
| | ACCESSIBLE AND COMPLY W/FACBC SEC.4.1.3 |
| | (10)(A). |
| | |
| | URINAL SHALL BE HANDICAP AND COMPLY W/ |
| | FACBC SEC.4.18. |