Plan Review Notes
Plan Review Notes For Permit 99080692
Permit Number 99080692
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00DENIED
 1) PROVIDE OUTSIDE AIR INFORMATION PER
 ASHRAE 62-89
 2) FAN SHUT DOWN BY DUCT SMOKE DETECTOR
 REQUIRED BY 1997 SMC 406.1
 PROVIDE INFORMATION AND SHALL BE TIED TO
 BUILDING FIRE ALARM OR HORN AND STROBE
 FOR NOTIFICATION PER NFPA 4-4.4.3