Plan Review Notes
Plan Review Notes For Permit 99080634
Permit Number 99080634
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************DENIED*******************
  
 1)NOTE:SHOW COMPLETE RISER DIAGRAM.
 TO INCLUDE ALL OF THE FOLLOWING:
 GROUNDING ELECTRODE CONDUCTOR TO GOT TO
 BLDG.STEEL ALSO 250-81
 )INCLUDE GARAGE DOOR OPENER IN LOAD
 CALCULATIONS AS IT REQ`S A DEDICATED
 CIRCUT.ALSO INCLUDE ON PANEL SCHED.
 )INCLUDE BATHROOMS ON PANEL SCHEDULE AS
 THEY ALSO REQ,DEDICATED CIRCUTS AS PER
 ART:210-52D
 )NOTE:GENERAL LIGHTING SHOWS 20AMP
 OVERCURRENT PROTECTION TO FEED #14 AWG.
 PLEASE MATCH AS PER 310-16
 )ONLY SHOW 15KW HEAT FIGURED IN THE LOAD
 CALCULATIONS,BUT SHOW OTHER HEAT STRIP
 AT 7.5 KW,,,,PLEASE FIGURE 7.5KW IN
 LOAD CALCULATIONS.
 2)NOTE:HOT WATER HEATER,DRYER,WASHER
 SHOWN TO BE ALL GFI,,,
 3)NOTE:AS PER 210-52G GFI RECEPT.REQ`D
 INSIDE GARAGE.
 4)NOTE:POWDERROOM IN FRONT OF HOUSE
 REQ`S GFI REC.AS PER 210-52D
 5)AS PER 1996 NFPA-72 2-2.1.1.1 REQ`S
 SMOKE DETECTORS INSIDE AND OUTSIDE
 BEDROOMS IN ALL NEW CONSTRUCTION HOMES.
 6)AS PER ART:210-52E GFI RECEPT.REQ`D
 FRONT OF DWELLING.
  
 7)PRINTS FROM WAUSAU HOMES SHOW FIRST
 FLOOR??? IF ADDITIONAL PANEL IS LOCATED
 IN SECOND FLOOR THEN IT MUST BE DRAWN
 ON RISER DIAGRAM ALSO.215-5
 PLEASE SUBMIT PLANS MARKED AS SECOND
 FLOOR ELECTRICAL PLANS.NOTE CODE FOR
 SMOKE DETECTORS LISTED ON THESE NOTES
 ABOVE.
 8)NOTE SUBMIT AIC RATING OF ALL EQUIP-
 -MENT AND BREAKERS BEING USED. AS PER
 ARTS:110-9 AND 215-5
  
 PLEASE SUBMIT ALL OF THE FOLLOWING.