| Plan Review Notes For Permit 99080620 |
| Permit Number |
99080620 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************UNSAT******************** | | | | | | 1)NOTE:COMPLETE INFORMATION REQ`EST ON | | | FIRST CORRECTION SHEET.YOU SHOW 80AMP | | | FEED TO PANEL"B" BUT SHOW PANEL "B" | | | WITH 88AMP LOAD.?????? | | | | | | THE ABOVE NEEDS TO BE TAKEN CARE OF | | | CORRECTED,SUBMITTED AND APPROVED BEFORE | | | FIRST ROUGH ELECTRICAL INSPECTION. | | | PANEL "B" 125 MAIN BRK PANEL SO IF WIRE | | | FEEDING PANEL IS INCREASED AND 80AMP | | | FUSES INCREASED THEN IT WILL MEET CODE. |
|