Plan Review Notes
Plan Review Notes For Permit 99080556
Permit Number 99080556
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00************PROVISO*********************
  
 1)NOTE:NEW PANEL AND DISC. ARE SHOWN ON
 RISER DIAGRAM FOR 10TH FLOOR,,PLEASE
 GIVE MORE DETAIL OF DISC.ALSO NEED TO
 SUBMIT AIC RATINGS OF NEW PANEL AND
 DISC.AND BRKRS BEING USED. AS PER ARTS;
 110-9 AND 215-5
 2) NOTE:NEED LOAD CACULATIONS OF 9TH
 FLOOR DISTR.PANEL. TO INCLUDE ALL
 PANELS AND EQUIPMENT BEING SUPPLIED
 BY THAT DISTR. PANEL.ART;215-5
 3)NEED TO SUBMIT LOAD CALCULATIONS OF
 MAIN DISTR.CENTER AT FIRST LEVEL.
  
 ALL THE ABOVE NEEDS TO BE DONE,SUBMITTED
 AND APPROVED BEFORE FIRST ELECTRICAL
 INSPECTION.