| Plan Review Notes For Permit 99080516 |
| Permit Number |
99080516 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | SUBMIT ONE SANITARY ISOMETRIC FOR REVIEW | | | THAT COMPLIES W/THE STD.PLBG.CODE.(THERE | | | ARE TWO DIFFERENT RISERS AND NEITHER | | | COMPLIES W/CODE.) SPC 104.2.1. | | | | | | SANITARY ISOMETRIC SHALL CORRELATE W/ | | | FLOOR PLAN.SPC 104.2.1. | | | | | | FIXTURES SHALL NOT EXCEED DISTANCES FROM | | | VENTS AS MANDATED IN TABLE 908 OF SPC. | | | | | | FIXTURES INSTALLED DOWNSTREAM OF WATER | | | CLOSETS SHALL BE VENTED PER SPC 913.2. | | | | | | NOT MORE THAN 4 FIXTURE UNITS SHALL | | | DISCHARGE INTO A 2" WET VENT PER SPC SEC | | | 911.1(1). | | | | | | BASE OF VENT FOR WATER CLOSET SHALL BE | | | WASHED PER SPC SEC.906.2.1. |
|