Plan Review Notes
Plan Review Notes For Permit 99080516
Permit Number 99080516
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00SUBMIT ONE SANITARY ISOMETRIC FOR REVIEW
 THAT COMPLIES W/THE STD.PLBG.CODE.(THERE
 ARE TWO DIFFERENT RISERS AND NEITHER
 COMPLIES W/CODE.) SPC 104.2.1.
  
 SANITARY ISOMETRIC SHALL CORRELATE W/
 FLOOR PLAN.SPC 104.2.1.
  
 FIXTURES SHALL NOT EXCEED DISTANCES FROM
 VENTS AS MANDATED IN TABLE 908 OF SPC.
  
 FIXTURES INSTALLED DOWNSTREAM OF WATER
 CLOSETS SHALL BE VENTED PER SPC 913.2.
  
 NOT MORE THAN 4 FIXTURE UNITS SHALL
 DISCHARGE INTO A 2" WET VENT PER SPC SEC
 911.1(1).
  
 BASE OF VENT FOR WATER CLOSET SHALL BE
 WASHED PER SPC SEC.906.2.1.